5.18 List of parameters
Parameter
Number of
elements
Unit of mea-
surement
Modification
Values interval
Degree of
precision
Predefined
setting
Access mode
No. par. Description Min. Max.
100 General parameters
102 Control box identification date 1 - Reading only 0 255 1 Info Mode
103 Control box identification number 1 - Reading only 0 65535 1 Info Mode
104 Identification number of the group of parameters set 1 - Reading only 0 255 1 Info Mode
105 Version of the group of parameters set 1 - Reading only 0 0xFFFF 1 Info Mode
107 Software version 1 - Reading only 0 0xFFFF 1 Info Mode
113 Burner identification 1 - Modification 0 99999999 1 Not defined Info Mode
121
Manual setting of output
Not defined = automatic operation
1-
Modification /
zero setting
0 % 100 % 0.1 % Not defined Service Mode
125
Frequency of main power supply
0 = 50 Hz
1 = 60 Hz
1 - Modification 0 1 1 0 Parameters Mode
126 Brightness of display 1 - Modification 0 % 100 % 1 % 75 % Parameters Mode
128
Fuel meter: Led pulse valence
(led pulses / volumetric flow units)
1 - Modification 0 400 0.01 0 Parameters Mode
130
Eliminate visualisation error chronology
To eliminate the visualisation, set the parameter to 1, then to 2
Answer 0: Process successful
Answer -1: Time-out of 1_2 - Sequence
1 - Modification -5 2 1 0 Parameters Mode
141
Remote management of control box
0 = off
1 = Modbus
2 = reserved
- Modification 0 2 1 0 Parameters Mode
142
Standby time before a new attempt in event of fault
in communication
s Modification 0 s 7200 s 1 s 600 s Parameters Mode
143 Reserved - Modification 1 8 1 1 Info Mode
144 Reserved - Modification 10 s 60 s 1 s 30 s Parameters Mode
145 Peripheral address for Modbus - Modification 1 247 1 1 Parameters Mode
146
Baud Rate for Modbus
0 = 9600
1 = 19200
- Modification 0 1 1 0 Parameters Mode
147
Parity for Modbus
0 = none
1 = odd
2 = even
1 - Modification 0 2 1 0 Parameters Mode