20
DIALOG DUAL
MODELS DLD 330 DLD 400 DLD 500 DLD 600 DLD 800 * DLD 1000 *
POWER
3300VA
2300W
4000VA
2400W
5000VA
3500W
6000VA
4200W
8000VA
5600W
10000VA
7000W
INPUT
Rated voltage 220 - 230 - 240 Vac
230 Vac single-phase or
400 Vac three-phase + N
Minimum voltage 164 Vac @ load 100% 84 Vac @ load 50%
Rated frequency 50/60 Hz ± 5 Hz
Power factor > 0.98 > 0.98 (in single/single-phase)
Current distortion ≤ 7% ≤ 5% ≤ 7% (in single/single-phase)
BY PASS
Voltage range 180 - 264 Vac (selectable in Economy Mode and SMART ACTIVE Mode)
Frequency range Selected frequency ±5 % (user configurable)
BATTERIES
Recharge time 2 - 4 h
OUTPUT
Rated voltage 220 - 230 - 240 Vac selectable
Static variation 1,5 %
Dynamic variation ≤ 5% in 20 ms
Wave form Sinewave
Voltage distortion with linear load < 3%
Voltage distortion with non-linear load
< 6%
Frequency 50/60 Hz selectable
Crest factor 3 : 1
OVERLOAD CAPACITY
100% < Load < 110% 1’ 1’
110% < Load < 125% 4 “ 1’
125% ≤ Load < 150% 4 “ 10”
Load > 150% 0.5 “ 0,5”
ENVIRONMENTAL
Weight (kg) 38 40 62 64 80 85
Dimensions (hwd) (mm) tower/rack
455x175x520/175(4U)x483x520 455x175x660/175(4U)x483x660 2x455x175x660/2x175(4U)x483x660
On Line Efficiency 92%
Line-interactive/Smart Active
Efficiency
98%
Operating temperature O °C - 40 °C
Relative humidity < 95% non condensing
Protection Overload - short-circuit - overvoltage - undervoltage - temperature - low battery
Compliance EN 62040-1 EMC EN 62040-2 Directives 73/23-93/68-89/336 EEC EN 62040-3
Communication USB / RS232 + communication interface slot
Colour metallic grey (silver)
Noise <40 dBA at 1 m <45 dBA at 1 m
Accessories provided
2x10A cables; 1xIEC-16A plug;
software; serial cable; plastic keys to
release display; handles kit
2 cable guides; terminal board connection; software; serial cable;
plastic keys to release display; handles kit
OPTIONS
Extended runtime solutions yes (with and without battery charger)
Internal Maintenance Bypass no yes
Interface cards yes
Telescopic rails for rack cabinet yes
* Available from the second half of 2006
NETWORK Range
Comentários a estes Manuais